STARTER TESYSH 0,75KW-400V CONTROL 110-2




SCDLZ1H2X4FU

Starter TeSys H 0,75kW-400V control 110-230VAC. range: TeSys - product name: TeSys H - device short name: LZ1H - product or component type: ultra-compact starter - poles description: 3P - [Ie] rated operational current: 2.4 A at 500 V AC-51, 2.4 A at 500 V AC-53A mounting side by side, 2.4 A at 500 V AC-53A, 2.4 A at 500 V AC-51 mounting side by side - motor power kW: 0.37 kW at 220 V AC with power factor : 0.65, 0.37 kW at 230 V AC with power factor : 0.65, 0.75 kW at 380 V AC with power factor : 0.65, 0.75 kW at 415 V AC with power factor : 0.65, 1.1 kW at 500 V AC with power factor : 0.65, 0.75 kW at 400 V AC with power factor : 0.65, 0.75 kW at 440 V AC with power factor : 0.65 - motor power hp: 0.5 hp at 230 V AC, 1 hp at 460 V AC, 0.5 hp at 200 V AC. Benefits: - Up to 75% space reduction, which makes it suitable for all control cabinets where saving space is a priority;, 60% reduction of installation time, thanks to the efficiency of having embedded functions in one slim body;, SIL3/Ple Safe Torque Off variant, simplies design of your safety architecture, A long electrical life, can perform 30million AC53a electrical cycles which make it reliable for high demanding applications.. Applications: TeSys H can be used in a variety of industries, including food and beverage, logistics, and durable goods. It's suitable for machines like conveyors, logistics systems and feeding systems of production machines..

Product Attributes

Ambient temperature, , upper operating limit 70 °C
Degree of protection (IP) IP20
Kind of motor starter Direct starter
Overload release current setting 0.18 A
Rail mounting possible Yes
Rated control supply voltage Us at AC 50HZ 110 V
Rated control supply voltage Us at AC 60HZ 110 V
Rated operation current Ie 2.4 A
Rated operation current at AC-3, 400 V 2.4 A
Rated operation power at AC-3, 230 V, 3-phase 0.37 kW
Rated operation power at AC-3, 400 V 0.75 kW
Rated power, 460 V, 60 Hz, 3-phase 0.75 kW
Release class CLASS 10
Supporting protocol for AS-Interface Safety at Work No
Supporting protocol for ASI No
Supporting protocol for CAN No
Supporting protocol for Data-Highway No
Supporting protocol for DeviceNet No
Supporting protocol for DeviceNet Safety No
Supporting protocol for EtherNet/IP No
Supporting protocol for Foundation Fieldbus No
Supporting protocol for INTERBUS No
Supporting protocol for INTERBUS-Safety No
Supporting protocol for LON No
Supporting protocol for MODBUS No
Supporting protocol for PROFIBUS No
Supporting protocol for PROFINET CBA No
Supporting protocol for PROFINET IO No
Supporting protocol for PROFIsafe No
Supporting protocol for SERCOS No
Supporting protocol for SUCONET No
Supporting protocol for SafetyBUS p No
Supporting protocol for TCP/IP No
Supporting protocol for other bus systems No
Temperature compensated overload protection Yes
Type of electrical connection for auxiliary- and control current circuit Screw connection
Type of electrical connection of main circuit Screw connection
Voltage type for actuating AC
With short-circuit release No
UOM Each